oPr on the Yaskawa GA500 is the “Keypad Connection Fault” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The drive stopped receiving messages from its controller (a PLC, a fieldbus master, a keypad or a network) within the allowed time. The drive itself is usually fine; the link to it is not.
- Code
- oPr
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Communication loss
01 / Causes
What causes oPr
- The keypad is not securely connected, or its cable is disconnected.
02 / Checks
What to check for oPr
In the order Yaskawa gives them.
- 01Check the keypad connection; remove and refit the keypad.
- 02Replace a damaged cable.
Also in the manual
- Detected when o2-06 = 1 and the run command comes from the keypad (b1-02 = 0 or LOCAL mode).
03 / Clearing it
How to clear oPr
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If oPr comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How communication loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the PLC or master is running and still sending to this drive.
- 02Check the communication cable, connectors and termination, and the screen's earth connection.
- 03Compare the drive's address, baud rate and timeout settings with the master's.
- 04Look for drives, contactors or welders near the cable that could be injecting noise.
05 / Repair
When oPr means a repair
If cable, settings and master are all good and only this drive drops out, its communication port or option card may have failed.
If oPr keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Communication loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F70 I/O Extension Module communication fault · F71 USS setpoint fault · F72 USS/MODBUS setpoint fault |
| Siemens SINAMICS G120 | F01910 Setpoint timeout · F08501 Setpoint timeout · F08502 Monitoring time, sign-of-life expired · F08510 Send configuration data not valid · F08700 Communications error · A01900 PROFIBUS: Configuration telegram faulty |
| Siemens SINAMICS V90 | F1030 Sign-of-life failure for master control · A1920 Drive Bus: Receive setpoints after To · A1932 Drive Bus clock cycle synchronization missing for DSC |
| Siemens MICROMASTER 440 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0710 CB communications error · A0711 CB communications error |
| Allen-Bradley PowerFlex 525 | F071 DSI Net Loss · F072 Opt Net Loss · F073 EN Net Loss · F081 DSI Comm Loss · F082 Opt Comm Loss · F083 EN Comm Loss |
| ABB ACS355 | F0010 PANEL LOSS · F0028 SERIAL 1 ERR · F0029 EFB CON FILE · A2005 IO COMM · A2008 PANEL LOSS · A5001 Drive is not responding |
| Delta VFD-E | cE01 Illegal function code · cE02 Illegal data address · cE03 Illegal data value · cE04 Slave device failure · cE10 Communication time-out |
| Delta C2000 | CE1 Illegal command · CE2 Illegal data address · CE3 Illegal data value · CE4 Data is written to read-only address · CE10 MODBUS transmission time-out · CGdE CANopen guarding error |
| Delta ASDA-B2 | AL019 Serial communication error · AL020 Serial communication time out |
| Hitachi WJ200 | E40 Operator connection · E41 Modbus communication error · E60 Option error (DeviceNet communications error) · E61 Option error (duplicated MAC ID) · E69 Option error (inverter communication error) |
| Schneider Electric Altivar ATV320 | CNF Fieldbus module communication interruption error · COF CANopen communication interruption error · SLF1 Modbus communication interruption error · SLF2 PC communication interruption error · SLF3 HMI communication interruption error |
| INVT Goodrive20 (GD20) | CE RS485 communication fault · PCE Keypad communication error · UPE Parameter upload error · DNE Parameter download error |
| Yaskawa V1000 | bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5 · oFA01 Option Card Fault · oFA03 Option Card Fault |
| Yaskawa A1000 | bUS Option Communication Error · CE MEMOBUS/Modbus Communication Error · E5 MECHATROLINK Watchdog Timer Error · oFA00 Option Card Connection Error at Option Port CN5-A · oFA01 Option Card Fault at Option Port CN5-A · oFb00 Option Card Fault at Option Port CN5-B |
| Siemens MICROMASTER 420 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3 |
| Siemens MICROMASTER 430 | F0070 CB setpoint fault · F0071 USS (BOP link) setpoint fault · F0072 USS (COMM link) setpoint fault · A0700 CB alarm 1 · A0701 CB alarm 2 · A0702 CB alarm 3 |
| Siemens SINAMICS G110 | F0072 USS setpoint fault |
| INVT Goodrive200A (GD200A) | CE RS485 communication fault · PCE Keypad communication fault · UPE Parameter upload error · DNE Parameter download error |
| Mitsubishi Electric FR-D700 | E.PUE PU disconnection |
| Danfoss VLT Micro Drive FC 51 | Alarm 17 Control word timeout · Error 84 The connection between drive and LCP is lost · Error 90 Parameter database busy |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007