ov on the Yaskawa GA500 is the “Overvoltage” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.
- Code
- ov
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- DC bus overvoltage
01 / Causes
What causes ov
- Deceleration or acceleration too short, too much braking load, surges on the supply, or the output cable or motor shorted to ground.
- Wrong speed search settings (during speed search, power-loss recovery or auto restart), supply voltage too high, braking resistor wiring wrong, or electrical interference.
- Load inertia set wrongly, Short Circuit Braking used in OLV/PM, motor hunting, or incomplete speed search with EZ Vector Control.
02 / Checks
What to check for ov
In the order Yaskawa gives them.
- 01Lengthen the deceleration times, fit a dynamic braking option, or do Deceleration Rate Tuning.
- 02Lengthen the acceleration times and C2-02, and set L3-11 = 1 (Overvoltage Suppression).
- 03Fit a DC link choke against supply surges (switched power factor capacitors or thyristor converters on the same supply can cause them).
- 04Remove ground faults from the motor cable, terminals and terminal box, then re-energize.
- 05Check the speed search settings: set b3-19 above 0, adjust b3-03, tune Line-to-Line Resistance and set b3-24 = 1; with an IE3 motor, double b3-03, L2-03 and L2-04.
- 06Bring the supply voltage within the drive's rating, and correct the braking resistor wiring.
- 07Examine the control circuit, main circuit and ground wiring, and reduce the effects of electrical interference.
- 08Adjust L3-25 (Load Inertia Ratio), and fit a braking resistor when using Short Circuit Braking in OLV/PM.
- 09For hunting, adjust n1-02, n2-02, n2-03, n8-45 and n8-47.
- 10With A1-02 = 8 (EZ Vector Control) and an induction motor (E9-01 = 0), speed search may not complete at start: set b3-24 = 2 (Current Detection Speed Search).
Also in the manual
- The trip level is about 410 V on 200 V class drives and about 820 V on 400 V class. As an alarm, ov is detected while the drive is stopped. L5-08 disables Auto Restart for this fault.
- The GA500 can also show this code as a minor fault or alarm: ALM/ERR flashes instead of staying lit, and the drive keeps running unless set to stop.
03 / Clearing it
How to clear ov
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If ov comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus overvoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
- 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
- 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
- 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.
05 / Repair
When ov means a repair
If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.
If ov keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
DC bus overvoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active |
| Siemens SINAMICS G120 | F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage |
| Siemens SINAMICS V90 | F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage |
| Siemens MICROMASTER 440 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Allen-Bradley PowerFlex 525 | F005 OverVoltage |
| ABB ACS355 | F0002 DC OVERVOLT · A2002 OVERVOLTAGE |
| Delta VFD-E | ov Over-voltage |
| Delta C2000 | ovA Over-voltage during acceleration · ovd Over-voltage during deceleration · ovn Over-voltage at constant speed · ovS Over-voltage at stop |
| Delta ASDA-B2 | AL002 Over voltage |
| Hitachi WJ200 | E07 Over-voltage protection · E15 Input over-voltage |
| Schneider Electric Altivar ATV320 | OBF DC bus overvoltage error · OSF Supply mains overvoltage error |
| INVT Goodrive20 (GD20) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Yaskawa V1000 | ov Overvoltage |
| Yaskawa A1000 | ov Overvoltage |
| Siemens MICROMASTER 420 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens MICROMASTER 430 | F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active |
| Siemens SINAMICS G110 | F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active |
| INVT Goodrive200A (GD200A) | OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running |
| Mitsubishi Electric FR-D700 | E.OV1 Regenerative overvoltage trip during acceleration · E.OV2 Regenerative overvoltage trip during constant speed · E.OV3 Regenerative overvoltage trip during deceleration or stop · oL Stall prevention (overvoltage) |
| Danfoss VLT Micro Drive FC 51 | Alarm 7 DC overvoltage |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007