PF on the Yaskawa GA500 is the “Input Phase Loss” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.
- Code
- PF
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Input phase loss
01 / Causes
What causes PF
- A phase missing from the input, loose input terminals, an unstable supply, or unbalanced phase voltages.
- The main circuit capacitors have become unserviceable.
02 / Checks
What to check for PF
In the order Yaskawa gives them.
- 01Correct the input wiring and tighten the terminal screws.
- 02Examine the supply and make it stable; if it is good, check the main circuit contactor.
- 03For unbalanced phase voltages, stabilise the supply or set L8-05 = 0 to disable input phase loss protection.
- 04Check the capacitor maintenance time (U4-05); above 90%, replace the control board or the drive.
Also in the manual
- Detected when the DC bus voltage changes irregularly without regeneration.
- The GA500 can also show this code as a minor fault or alarm: ALM/ERR flashes instead of staying lit, and the drive keeps running unless set to stop.
03 / Clearing it
How to clear PF
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If PF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How input phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure all three phases at the drive input terminals with the drive running under load.
- 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
- 03Tighten and inspect supply terminals for heat damage.
05 / Repair
When PF means a repair
If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.
If PF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Input phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F20 DC ripple too high |
| Siemens SINAMICS G120 | F30011 Line phase failure |
| Siemens SINAMICS V90 | F30011 Line phase failure in main circuit |
| Siemens MICROMASTER 440 | F0020 Line supply phase missing |
| ABB ACS355 | F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS |
| Delta VFD-E | PHL Phase loss |
| Delta C2000 | OrP Phase loss protection |
| Delta ASDA-B2 | AL022 Main circuit power lack phase |
| Schneider Electric Altivar ATV320 | PHF Input phase loss error |
| INVT Goodrive20 (GD20) | SPI Phase loss on input side |
| Yaskawa V1000 | PF Input Phase Loss |
| Yaskawa A1000 | PF Input Phase Loss |
| Siemens MICROMASTER 430 | F0020 Line supply phase missing |
| INVT Goodrive200A (GD200A) | SPI Phase loss on input side |
| Mitsubishi Electric FR-D700 | E.ILF Input phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 4 Mains phase loss |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007