MachineryFix

ABB AC drive (VFD) · alarm code

ACS355 A2002: OVERVOLTAGE

A2002 on the ABB ACS355 is the “OVERVOLTAGE” alarm. An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.

The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.

Code
A2002
Type
Alarm (warning)
Drive
ABB ACS355
Kind of fault
DC bus overvoltage

01 / Causes

What causes A2002

  • The DC overvoltage controller is active.

02 / Checks

What to check for A2002

In the order ABB gives them.

  1. 01Check the input voltage, and check the power line for static or transient overvoltage.
  2. 02If the drive is on a floating (IT) network, remove the drive's EMC screw.
  3. 03If the trip comes during deceleration: check the overvoltage controller is on (parameter 2005 OVERVOLT CTRL), lengthen the deceleration time (2203, 2206), and check the brake chopper and resistor if fitted.
  4. 04When a brake chopper and resistor are used, the DC overvoltage controller must be turned off (2005). A drive without one can be fitted with a brake chopper and resistor.

Also in the manual

  • ABB's alarm table refers to fault F0002 for the causes and checks, which are repeated here.
  • ABB lists this as a programmable fault function: parameters 1610 decide whether the condition is reported and how the drive reacts.

03 / Clearing it

How to clear A2002

An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.

If A2002 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How dc bus overvoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
  2. 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
  3. 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
  4. 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.

05 / Repair

When A2002 means a repair

If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.

If A2002 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.

06 / Other drives

DC bus overvoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active
Siemens SINAMICS G120F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage
Siemens SINAMICS V90F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage
Siemens MICROMASTER 440F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Allen-Bradley PowerFlex 525F005 OverVoltage
Delta VFD-Eov Over-voltage
Delta C2000ovA Over-voltage during acceleration · ovd Over-voltage during deceleration · ovn Over-voltage at constant speed · ovS Over-voltage at stop
Delta ASDA-B2AL002 Over voltage
Hitachi WJ200E07 Over-voltage protection · E15 Input over-voltage
Schneider Electric Altivar ATV320OBF DC bus overvoltage error · OSF Supply mains overvoltage error
INVT Goodrive20 (GD20)OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running
Yaskawa V1000ov Overvoltage
Yaskawa A1000ov Overvoltage
Yaskawa GA500ov Overvoltage
Siemens MICROMASTER 420F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens MICROMASTER 430F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens SINAMICS G110F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active
INVT Goodrive200A (GD200A)OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running
Mitsubishi Electric FR-D700E.OV1 Regenerative overvoltage trip during acceleration · E.OV2 Regenerative overvoltage trip during constant speed · E.OV3 Regenerative overvoltage trip during deceleration or stop · oL Stall prevention (overvoltage)
Danfoss VLT Micro Drive FC 51Alarm 7 DC overvoltage

07 / More codes

Other ACS355 codes

Source

ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

A2002 won't clear? Get a technician who knows the ACS355.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.