PowerFlex 525 F040: Phase W to Gnd

F040 on the Allen-Bradley PowerFlex 525 is the “Phase W to Gnd” fault. A fault stops the drive; it will not restart until the fault is cleared.

The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.

Code
F040
Type
Fault (stops the drive)
Drive
Allen-Bradley PowerFlex 525, PowerFlex 523
Kind of fault
Earth fault

01 / Causes

What causes F040

Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing earth fault faults explains where it usually comes from.

02 / Checks

What to check for F040

In the order Rockwell Automation gives them.

  1. 01Check the wiring between the drive and the motor.
  2. 02Check the motor for a grounded phase.
  3. 03Replace the drive if the fault cannot be cleared.

03 / Clearing it

How to clear F040

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

Clear it once. If F040 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How earth fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
  2. 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
  3. 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
  4. 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
  5. 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.

05 / Repair

When F040 means a repair

When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.

If F040 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.

06 / Other drives

Earth fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F30021 Ground fault
Siemens SINAMICS V90F30021 Ground fault
Siemens MICROMASTER 440F0021 Ground fault
ABB ACS355F0016 EARTH FAULT
Delta VFD-EGFF Ground fault
Delta C2000GFF Ground fault
Hitachi WJ200E14 Ground fault
Schneider Electric Altivar ATV320SCF3 Ground short circuit error
INVT Goodrive20 (GD20)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Yaskawa V1000GF Ground Fault
Yaskawa A1000GF Ground Fault
Yaskawa GA500GF Ground Fault
Siemens MICROMASTER 430F0021 Ground fault
INVT Goodrive200A (GD200A)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Mitsubishi Electric FR-D700E.GF Output side earth (ground) fault overcurrent at start
Danfoss VLT Micro Drive FC 51Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2

07 / More codes

Other PowerFlex 525 codes

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F040 won't clear? Get a technician who knows the PowerFlex 525.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.