oH1 on the Delta C2000 is the “IGBT overheating” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.
- Code
- oH1
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- Drive overtemperature
01 / Causes
What causes oH1
- The ambient or cabinet temperature is too high, or the cabinet's ventilation holes are blocked.
- The heatsink is blocked or the cooling fan is not running.
- Not enough ventilation space around the drive.
- The drive is too small for the load.
- The drive has run at 100% of its rated output or more for a long time.
02 / Checks
What to check for oH1
In the order Delta Electronics gives them.
- 01Check the ambient temperature and inspect the cabinet's ventilation holes regularly.
- 02Move the drive away from heat sources such as braking resistors, or add a cooling fan or air conditioning to the cabinet.
- 03Clear anything blocking the heatsink, or replace the cooling fan.
- 04Give the drive more ventilation space.
- 05Reduce the load or the carrier frequency, or fit a larger drive.
Also in the manual
- Fault ID 16. The IGBT temperature stayed above its protection level for more than 100 ms. Resets once the IGBT temperature is 10°C below the oH1 level.
- Below the fault level the drive gives an oH1 warning first, at the level set in Pr. 06-15; the fault and warning levels for each model are tabled in the manual.
03 / Clearing it
How to clear oH1
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If oH1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
- 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
- 03Measure the temperature inside the panel and check the panel fans and filters.
- 04Check the switching frequency against the factory setting and the load current against the drive's rating.
05 / Repair
When oH1 means a repair
A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.
If oH1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Drive overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning |
| Siemens SINAMICS G120 | F30004 Inverter overtemperature · F30035 Overtemperature, intake air · F30036 Overtemperature, inside area · F30037 Rectifier overtemperature · A05000 Power Module overtemperature · A05001 Power Module overtemperature |
| Siemens SINAMICS V90 | F30004 Drive heat sink overtemperature · F30036 Internal overtemperature · A1009 Control module overtemperature · A5000 Drive heat sink overtemperature |
| Siemens MICROMASTER 440 | F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high |
| Allen-Bradley PowerFlex 525 | F008 Heatsink OvrTmp · F009 CC OvrTmp |
| ABB ACS355 | F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP |
| Delta VFD-E | oH1 IGBT overheat · oH2 Power board overheat |
| Delta ASDA-B2 | AL016 IGBT overheat |
| Hitachi WJ200 | E21 Inverter thermal trip |
| Schneider Electric Altivar ATV320 | OHF Drive overheating error · TJF IGBT overheating |
| INVT Goodrive20 (GD20) | OH1 Rectifier module overheat · OH2 Inverter module overheat |
| Yaskawa V1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) |
| Yaskawa A1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) · oH2 Heatsink Overheat Warning |
| Yaskawa GA500 | oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B) |
| Siemens MICROMASTER 420 | F0004 Inverter overtemperature · A0504 Inverter overtemperature |
| Siemens MICROMASTER 430 | F0004 Inverter overtemperature · A0504 Inverter overtemperature |
| Siemens SINAMICS G110 | F0004 Inverter over temperature |
| INVT Goodrive200A (GD200A) | OH1 Rectifier module overheating · OH2 Inverter module overheat |
| Mitsubishi Electric FR-D700 | E.FIN Heatsink overheat |
| Danfoss VLT Micro Drive FC 51 | Alarm 29 Heat sink temperature |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007