F009 on the Allen-Bradley PowerFlex 525 is the “CC OvrTmp” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.
- Code
- F009
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Drive overtemperature
01 / Causes
What causes F009
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing drive overtemperature faults explains where it usually comes from.
02 / Checks
What to check for F009
In the order Rockwell Automation gives them.
- 01Check the product's ambient temperature.
- 02Check for an airflow obstruction.
- 03Check for dirt or debris.
- 04Check the fan.
03 / Clearing it
How to clear F009
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F009 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
- 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
- 03Measure the temperature inside the panel and check the panel fans and filters.
- 04Check the switching frequency against the factory setting and the load current against the drive's rating.
05 / Repair
When F009 means a repair
A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.
If F009 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Drive overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning |
| Siemens SINAMICS G120 | F30004 Inverter overtemperature · F30035 Overtemperature, intake air · F30036 Overtemperature, inside area · F30037 Rectifier overtemperature · A05000 Power Module overtemperature · A05001 Power Module overtemperature |
| Siemens SINAMICS V90 | F30004 Drive heat sink overtemperature · F30036 Internal overtemperature · A1009 Control module overtemperature · A5000 Drive heat sink overtemperature |
| Siemens MICROMASTER 440 | F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high |
| ABB ACS355 | F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP |
| Delta VFD-E | oH1 IGBT overheat · oH2 Power board overheat |
| Delta C2000 | oH1 IGBT overheating · oH2 Heatsink overheating |
| Delta ASDA-B2 | AL016 IGBT overheat |
| Hitachi WJ200 | E21 Inverter thermal trip |
| Schneider Electric Altivar ATV320 | OHF Drive overheating error · TJF IGBT overheating |
| INVT Goodrive20 (GD20) | OH1 Rectifier module overheat · OH2 Inverter module overheat |
| Yaskawa V1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) |
| Yaskawa A1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) · oH2 Heatsink Overheat Warning |
| Yaskawa GA500 | oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B) |
| Siemens MICROMASTER 420 | F0004 Inverter overtemperature · A0504 Inverter overtemperature |
| Siemens MICROMASTER 430 | F0004 Inverter overtemperature · A0504 Inverter overtemperature |
| Siemens SINAMICS G110 | F0004 Inverter over temperature |
| INVT Goodrive200A (GD200A) | OH1 Rectifier module overheating · OH2 Inverter module overheat |
| Mitsubishi Electric FR-D700 | E.FIN Heatsink overheat |
| Danfoss VLT Micro Drive FC 51 | Alarm 29 Heat sink temperature |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007