MachineryFix

Siemens Servo drive · fault code

SINAMICS V90 F30036: Internal overtemperature

F30036 on the Siemens SINAMICS V90 is the “Internal overtemperature” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.

The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.

Code
F30036
Type
Fault (stops the drive)
Drive
Siemens SINAMICS V90, SIMOTICS S-1FL6
Kind of fault
Drive overtemperature

01 / Causes

What causes F30036

  • Insufficient cooling, or the fan has failed.
  • Overload.
  • The surrounding temperature is too high.

02 / Checks

What to check for F30036

In the order Siemens gives them.

  1. 01Check the fan is running.
  2. 02Check the fan elements.
  3. 03Check the surrounding temperature is in the permissible range.

Also in the manual

  • Reaction OFF2: the motor coasts down. Acknowledgement IMMEDIATELY: it clears as soon as the cause is removed.
  • The temperature inside the converter went above its limit. It can only be acknowledged once the temperature is 5 K below the limit.

03 / Clearing it

How to clear F30036

  • Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
  • Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
  • If the cause is not removed, the fault can come back after five seconds with no button pressed.
  • Alarms acknowledge themselves.

Clear it once. If F30036 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How drive overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
  2. 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
  3. 03Measure the temperature inside the panel and check the panel fans and filters.
  4. 04Check the switching frequency against the factory setting and the load current against the drive's rating.

05 / Repair

When F30036 means a repair

A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.

If F30036 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Drive overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning
Siemens SINAMICS G120F30004 Inverter overtemperature · F30035 Overtemperature, intake air · F30036 Overtemperature, inside area · F30037 Rectifier overtemperature · A05000 Power Module overtemperature · A05001 Power Module overtemperature
Siemens MICROMASTER 440F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high
Allen-Bradley PowerFlex 525F008 Heatsink OvrTmp · F009 CC OvrTmp
ABB ACS355F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP
Delta VFD-EoH1 IGBT overheat · oH2 Power board overheat
Delta C2000oH1 IGBT overheating · oH2 Heatsink overheating
Delta ASDA-B2AL016 IGBT overheat
Hitachi WJ200E21 Inverter thermal trip
Schneider Electric Altivar ATV320OHF Drive overheating error · TJF IGBT overheating
INVT Goodrive20 (GD20)OH1 Rectifier module overheat · OH2 Inverter module overheat
Yaskawa V1000oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat)
Yaskawa A1000oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) · oH2 Heatsink Overheat Warning
Yaskawa GA500oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B)
Siemens MICROMASTER 420F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens MICROMASTER 430F0004 Inverter overtemperature · A0504 Inverter overtemperature
Siemens SINAMICS G110F0004 Inverter over temperature
INVT Goodrive200A (GD200A)OH1 Rectifier module overheating · OH2 Inverter module overheat
Mitsubishi Electric FR-D700E.FIN Heatsink overheat
Danfoss VLT Micro Drive FC 51Alarm 29 Heat sink temperature

07 / More codes

Other SINAMICS V90 codes

Source

Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F30036 won't clear? Get a technician who knows the SINAMICS V90.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.