F30037 on the Siemens SINAMICS G120 is the “Rectifier overtemperature” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.
The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.
- Code
- F30037
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS G120, CU240B-2, CU240E-2
- Kind of fault
- Drive overtemperature
01 / Causes
What causes F30037
Siemens's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing drive overtemperature faults explains where it usually comes from.
02 / Checks
What to check for F30037
In the order Siemens gives them.
- 01Check whether the fan is running.
- 02Check the fan's filter elements.
- 03Check the ambient temperature is in the permissible range.
- 04Check the motor load.
- 05Check the line phases.
03 / Clearing it
How to clear F30037
- Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
- Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
- Alarms need no acknowledgement: they disappear once the cause is removed.
Clear it once. If F30037 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
- 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
- 03Measure the temperature inside the panel and check the panel fans and filters.
- 04Check the switching frequency against the factory setting and the load current against the drive's rating.
05 / Repair
When F30037 means a repair
A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.
If F30037 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Drive overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning |
| Siemens SINAMICS V90 | F30004 Drive heat sink overtemperature · F30036 Internal overtemperature · A1009 Control module overtemperature · A5000 Drive heat sink overtemperature |
| Siemens MICROMASTER 440 | F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high |
| Allen-Bradley PowerFlex 525 | F008 Heatsink OvrTmp · F009 CC OvrTmp |
| ABB ACS355 | F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP |
| Delta VFD-E | oH1 IGBT overheat · oH2 Power board overheat |
| Delta C2000 | oH1 IGBT overheating · oH2 Heatsink overheating |
| Delta ASDA-B2 | AL016 IGBT overheat |
| Hitachi WJ200 | E21 Inverter thermal trip |
| Schneider Electric Altivar ATV320 | OHF Drive overheating error · TJF IGBT overheating |
| INVT Goodrive20 (GD20) | OH1 Rectifier module overheat · OH2 Inverter module overheat |
| Yaskawa V1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) |
| Yaskawa A1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) · oH2 Heatsink Overheat Warning |
| Yaskawa GA500 | oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B) |
| Siemens MICROMASTER 420 | F0004 Inverter overtemperature · A0504 Inverter overtemperature |
| Siemens MICROMASTER 430 | F0004 Inverter overtemperature · A0504 Inverter overtemperature |
| Siemens SINAMICS G110 | F0004 Inverter over temperature |
| INVT Goodrive200A (GD200A) | OH1 Rectifier module overheating · OH2 Inverter module overheat |
| Mitsubishi Electric FR-D700 | E.FIN Heatsink overheat |
| Danfoss VLT Micro Drive FC 51 | Alarm 29 Heat sink temperature |
07 / More codes
Other SINAMICS G120 codes
Source
Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007