MachineryFix

Siemens AC drive (VFD) · fault code

MICROMASTER 440 F0021: Ground fault

F0021 on the Siemens MICROMASTER 440 is the “Ground fault” fault. On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset.

The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.

Code
F0021
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 440
Kind of fault
Earth fault

01 / Causes

What causes F0021

  • The sum of the phase currents is more than 5% of the inverter's rated current.

02 / Checks

What to check for F0021

In the order Siemens gives them.

  1. 01Check the connections in the motor terminal box.
  2. 02Check the motor cable connections at the inverter.

Also in the manual

  • F0021 only occurs on inverters with three current sensors (frame sizes D to F, FX and GX).

03 / Clearing it

How to clear F0021

  • Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0021 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How earth fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
  2. 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
  3. 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
  4. 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
  5. 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.

05 / Repair

When F0021 means a repair

When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.

If F0021 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Earth fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F30021 Ground fault
Siemens SINAMICS V90F30021 Ground fault
Allen-Bradley PowerFlex 525F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd
ABB ACS355F0016 EARTH FAULT
Delta VFD-EGFF Ground fault
Delta C2000GFF Ground fault
Hitachi WJ200E14 Ground fault
Schneider Electric Altivar ATV320SCF3 Ground short circuit error
INVT Goodrive20 (GD20)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Yaskawa V1000GF Ground Fault
Yaskawa A1000GF Ground Fault
Yaskawa GA500GF Ground Fault
Siemens MICROMASTER 430F0021 Ground fault
INVT Goodrive200A (GD200A)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Mitsubishi Electric FR-D700E.GF Output side earth (ground) fault overcurrent at start
Danfoss VLT Micro Drive FC 51Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2

07 / More codes

Other MICROMASTER 440 codes

Source

Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0021 won't clear? Get a technician who knows the MICROMASTER 440.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.