MICROMASTER 440 F0020: Line supply phase missing

F0020 on the Siemens MICROMASTER 440 is the “Line supply phase missing” fault. On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset.

One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.

Code
F0020
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 440
Kind of fault
Input phase loss

01 / Causes

What causes F0020

  • One of the three input phases is missing while the pulses are enabled and a load is connected.

02 / Checks

What to check for F0020

In the order Siemens gives them.

  1. 01Check the power connections.

03 / Clearing it

How to clear F0020

  • Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0020 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How input phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure all three phases at the drive input terminals with the drive running under load.
  2. 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
  3. 03Tighten and inspect supply terminals for heat damage.

05 / Repair

When F0020 means a repair

If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.

If F0020 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Input phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F20 DC ripple too high
Siemens SINAMICS G120F30011 Line phase failure
Siemens SINAMICS V90F30011 Line phase failure in main circuit
ABB ACS355F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS
Delta VFD-EPHL Phase loss
Delta C2000OrP Phase loss protection
Delta ASDA-B2AL022 Main circuit power lack phase
Schneider Electric Altivar ATV320PHF Input phase loss error
INVT Goodrive20 (GD20)SPI Phase loss on input side
Yaskawa V1000PF Input Phase Loss
Yaskawa A1000PF Input Phase Loss
Yaskawa GA500PF Input Phase Loss
Siemens MICROMASTER 430F0020 Line supply phase missing
INVT Goodrive200A (GD200A)SPI Phase loss on input side
Mitsubishi Electric FR-D700E.ILF Input phase loss
Danfoss VLT Micro Drive FC 51Alarm 4 Mains phase loss

07 / More codes

Other MICROMASTER 440 codes

Source

Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0020 won't clear? Get a technician who knows the MICROMASTER 440.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.