SINAMICS G120 F30021: Ground fault

F30021 on the Siemens SINAMICS G120 is the “Ground fault” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.

The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.

Code
F30021
Type
Fault (stops the drive)
Drive
Siemens SINAMICS G120, CU240B-2, CU240E-2
Kind of fault
Earth fault

01 / Causes

What causes F30021

Siemens's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing earth fault faults explains where it usually comes from.

02 / Checks

What to check for F30021

In the order Siemens gives them.

  1. 01Check the power cable connections.
  2. 02Check the motor.
  3. 03Check the current transformer.
  4. 04Check the cables and contacts of the brake connection, in case a wire is broken.

03 / Clearing it

How to clear F30021

  • Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
  • Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
  • Alarms need no acknowledgement: they disappear once the cause is removed.

Clear it once. If F30021 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How earth fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
  2. 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
  3. 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
  4. 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
  5. 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.

05 / Repair

When F30021 means a repair

When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.

If F30021 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Earth fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V90F30021 Ground fault
Siemens MICROMASTER 440F0021 Ground fault
Allen-Bradley PowerFlex 525F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd
ABB ACS355F0016 EARTH FAULT
Delta VFD-EGFF Ground fault
Delta C2000GFF Ground fault
Hitachi WJ200E14 Ground fault
Schneider Electric Altivar ATV320SCF3 Ground short circuit error
INVT Goodrive20 (GD20)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Yaskawa V1000GF Ground Fault
Yaskawa A1000GF Ground Fault
Yaskawa GA500GF Ground Fault
Siemens MICROMASTER 430F0021 Ground fault
INVT Goodrive200A (GD200A)ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2
Mitsubishi Electric FR-D700E.GF Output side earth (ground) fault overcurrent at start
Danfoss VLT Micro Drive FC 51Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2

07 / More codes

Other SINAMICS G120 codes

Source

Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F30021 won't clear? Get a technician who knows the SINAMICS G120.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.