SINAMICS V20 F20: DC ripple too high

F20 on the Siemens SINAMICS V20 is the “DC ripple too high” fault. A fault stops the inverter's output; the motor will not run again until the fault is cleared.

One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.

Code
F20
Type
Fault (stops the drive)
Drive
Siemens SINAMICS V20
Kind of fault
Input phase loss

01 / Causes

What causes F20

  • The calculated DC ripple has exceeded the safe threshold, most commonly because one mains input phase has been lost.

02 / Checks

What to check for F20

In the order Siemens gives them.

  1. 01Check the mains supply wiring.

03 / Clearing it

How to clear F20

  • Clear or acknowledge a fault from the BOP, or externally if the inverter is set up for it.
  • Holding the function key for more than two seconds shows the inverter's status at the moment of the fault.
  • Some faults (F64, F350) can only be cleared by switching the power off and on, and F5 cannot be cleared until the inverter's overload utilisation has fallen below its warning level.

Clear it once. If F20 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How input phase loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure all three phases at the drive input terminals with the drive running under load.
  2. 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
  3. 03Tighten and inspect supply terminals for heat damage.

05 / Repair

When F20 means a repair

If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.

If F20 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Input phase loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F30011 Line phase failure
Siemens SINAMICS V90F30011 Line phase failure in main circuit
Siemens MICROMASTER 440F0020 Line supply phase missing
ABB ACS355F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS
Delta VFD-EPHL Phase loss
Delta C2000OrP Phase loss protection
Delta ASDA-B2AL022 Main circuit power lack phase
Schneider Electric Altivar ATV320PHF Input phase loss error
INVT Goodrive20 (GD20)SPI Phase loss on input side
Yaskawa V1000PF Input Phase Loss
Yaskawa A1000PF Input Phase Loss
Yaskawa GA500PF Input Phase Loss
Siemens MICROMASTER 430F0020 Line supply phase missing
INVT Goodrive200A (GD200A)SPI Phase loss on input side
Mitsubishi Electric FR-D700E.ILF Input phase loss
Danfoss VLT Micro Drive FC 51Alarm 4 Mains phase loss

07 / More codes

Other SINAMICS V20 codes

Source

Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F20 won't clear? Get a technician who knows the SINAMICS V20.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.