F5 on the Siemens SINAMICS V20 is the “Inverter I2t” fault. A fault stops the inverter's output; the motor will not run again until the fault is cleared.
The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.
- Code
- F5
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V20
- Kind of fault
- Drive overload
01 / Causes
What causes F5
- The inverter is overloaded.
- The load cycle is too demanding.
- The motor power (P0307) is more than the inverter can supply (r0206).
02 / Checks
What to check for F5
In the order Siemens gives them.
- 01Make sure the load cycle is within the specified limits.
- 02Make sure the motor power (P0307) matches the inverter power (r0206).
Also in the manual
- F5 cannot be cleared until the inverter overload utilisation (r0036) has fallen below the inverter I2t warning level (P0294).
03 / Clearing it
How to clear F5
- Clear or acknowledge a fault from the BOP, or externally if the inverter is set up for it.
- Holding the function key for more than two seconds shows the inverter's status at the moment of the fault.
- Some faults (F64, F350) can only be cleared by switching the power off and on, and F5 cannot be cleared until the inverter's overload utilisation has fallen below its warning level.
Clear it once. If F5 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overload faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Record the running current and compare it with the drive's rated current.
- 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
- 03Check acceleration time and boost settings; long periods at high torque add up quickly.
05 / Repair
When F5 means a repair
If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.
If F5 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Drive overload: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t |
| Siemens SINAMICS V90 | F30005 Power unit: Overload I2t |
| Siemens MICROMASTER 440 | F0005 Inverter I2T · A0505 Inverter I2T |
| Allen-Bradley PowerFlex 525 | F064 Drive Overload |
| Delta VFD-E | oL Overload |
| Delta C2000 | oL Over load · oL3 Overload protection at low frequency |
| Hitachi WJ200 | E38 Low-speed overload protection |
| INVT Goodrive20 (GD20) | OL2 VFD overload |
| Yaskawa V1000 | oL2 Drive Overload |
| Yaskawa A1000 | oL2 Drive Overload |
| Yaskawa GA500 | oL2 Drive Overload |
| Siemens MICROMASTER 420 | F0005 Inverter I2t · A0505 Inverter I2t |
| Siemens MICROMASTER 430 | F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle |
| Siemens SINAMICS G110 | F0005 Inverter I2t · A0505 Inverter I2t |
| INVT Goodrive200A (GD200A) | OL2 VFD overload |
| Mitsubishi Electric FR-D700 | E.THT Inverter overload trip (electronic thermal O/L relay function) |
| Danfoss VLT Micro Drive FC 51 | Alarm 9 Inverter overloaded |
07 / More codes
Other SINAMICS V20 codes
Source
Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007