PF on the Yaskawa V1000 is the “Input Phase Loss” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
One of the three supply phases is missing or weak, so the DC bus ripple rose above a safe level. Running on two phases overloads the rectifier and the capacitors.
- Code
- PF
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- Input phase loss
01 / Causes
What causes PF
- The input supply has an open phase or a large voltage imbalance between phases (detected when L8-05 = 1).
- A missing phase, loose input terminals, large supply fluctuations, poor phase balance, or worn main circuit capacitors.
02 / Checks
What to check for PF
In the order Yaskawa gives them.
- 01Check and correct the main circuit input wiring.
- 02Tighten the input terminals to the torque in the manual.
- 03Check the supply voltage and stabilise it.
- 04Check the capacitor maintenance time (U4-05) and replace the drive if it is above 90%.
- 05Phase loss detection can be turned off (L8-05 = 0), but Yaskawa warns the high DC bus ripple remains and shortens the capacitors' life.
03 / Clearing it
How to clear PF
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If PF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How input phase loss faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Measure all three phases at the drive input terminals with the drive running under load.
- 02Check input fuses, the breaker and the contactor for a blown fuse or a burnt contact.
- 03Tighten and inspect supply terminals for heat damage.
05 / Repair
When PF means a repair
If all three phases are healthy at the terminals and the code persists, the drive's rectifier or its supply sensing is at fault.
If PF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Input phase loss: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F20 DC ripple too high |
| Siemens SINAMICS G120 | F30011 Line phase failure |
| Siemens SINAMICS V90 | F30011 Line phase failure in main circuit |
| Siemens MICROMASTER 440 | F0020 Line supply phase missing |
| ABB ACS355 | F0022 SUPPLY PHASE · A2026 INPUT PHASE LOSS |
| Delta VFD-E | PHL Phase loss |
| Delta C2000 | OrP Phase loss protection |
| Delta ASDA-B2 | AL022 Main circuit power lack phase |
| Schneider Electric Altivar ATV320 | PHF Input phase loss error |
| INVT Goodrive20 (GD20) | SPI Phase loss on input side |
| Yaskawa A1000 | PF Input Phase Loss |
| Yaskawa GA500 | PF Input Phase Loss |
| Siemens MICROMASTER 430 | F0020 Line supply phase missing |
| INVT Goodrive200A (GD200A) | SPI Phase loss on input side |
| Mitsubishi Electric FR-D700 | E.ILF Input phase loss |
| Danfoss VLT Micro Drive FC 51 | Alarm 4 Mains phase loss |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007