oL1 on the Yaskawa V1000 is the “Motor Overload” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.
- Code
- oL1
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- Motor overload or overtemperature
01 / Causes
What causes oL1
- The drive's electrothermal motor protection tripped.
- Short acceleration and deceleration cycles, overload at low speed (a general-purpose motor can overload at low speed even within rated current), the wrong motor protection type in L1-01, a V/f voltage too high, a wrong E2-01 or base frequency, several motors on one drive, overexcitation, wrong Speed Search settings, or current fluctuation from an input phase loss.
02 / Checks
What to check for oL1
In the order Yaskawa gives them.
- 01Lengthen the acceleration and deceleration times (C1-01 to C1-08).
- 02Reduce the load or increase the speed; for sustained low-speed duty, use a larger motor or one designed for drive operation.
- 03For a special motor, set L1-01 to 2.
- 04If the voltage is too high for the V/f pattern, adjust E1-04 to E1-10, mainly by lowering E1-08 and E1-10, but not so far that the motor loses load tolerance at low speed.
- 05Enter the nameplate rated current in E2-01 and the rated frequency in E1-06.
- 06With several motors on one drive, set L1-01 to 0 and fit a thermal relay to each motor.
- 07Limit overexcitation: reduce n3-13 and set L3-04 to something other than 4.
- 08Check the Speed Search settings (b3-02, b3-03) and, after Auto-Tuning, enable Speed Estimation Type search (b3-24 = 1).
- 09Check the supply for a missing phase.
Also in the manual
- oL1 cannot be reset until monitor U4-16 is below 100.
03 / Clearing it
How to clear oL1
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If oL1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor overload or overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare running current with the motor's rating plate current.
- 02Check the motor overload settings in the drive against the rating plate.
- 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
- 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.
05 / Repair
When oL1 means a repair
A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.
If oL1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Motor overload or overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F11 Motor overtemperature · A511 Motor overtemperature I2t |
| Siemens SINAMICS G120 | F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature |
| Siemens SINAMICS V90 | F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature |
| Siemens MICROMASTER 440 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Allen-Bradley PowerFlex 525 | F007 Motor Overload |
| ABB ACS355 | F0009 MOT OVERTEMP · A2010 MOTOR TEMP |
| Delta VFD-E | oL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection |
| Delta C2000 | EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating |
| Delta ASDA-B2 | AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload |
| Hitachi WJ200 | E05 Overload protection · E35 Thermistor |
| Schneider Electric Altivar ATV320 | OLF Motor overload error · OTFL DI6=PTC overheat error |
| INVT Goodrive20 (GD20) | OL1 Motor overload |
| Yaskawa A1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload |
| Yaskawa GA500 | oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Siemens MICROMASTER 420 | F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t |
| Siemens MICROMASTER 430 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Siemens SINAMICS G110 | F0011 Motor over temperature I2t · A0511 Motor over temperature I2t |
| INVT Goodrive200A (GD200A) | OL1 Motor overload |
| Mitsubishi Electric FR-D700 | E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 10 Motor ETR over temperature |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007