F007 on the Allen-Bradley PowerFlex 525 is the “Motor Overload” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.
- Code
- F007
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Motor overload or overtemperature
01 / Causes
What causes F007
- An excessive motor load.
02 / Checks
What to check for F007
In the order Rockwell Automation gives them.
- 01Reduce the load so the drive's output current does not exceed the motor overload current set in P033 [Motor OL Current].
- 02Check the A530 [Boost Select] setting.
03 / Clearing it
How to clear F007
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F007 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor overload or overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare running current with the motor's rating plate current.
- 02Check the motor overload settings in the drive against the rating plate.
- 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
- 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.
05 / Repair
When F007 means a repair
A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.
If F007 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Motor overload or overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F11 Motor overtemperature · A511 Motor overtemperature I2t |
| Siemens SINAMICS G120 | F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature |
| Siemens SINAMICS V90 | F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature |
| Siemens MICROMASTER 440 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| ABB ACS355 | F0009 MOT OVERTEMP · A2010 MOTOR TEMP |
| Delta VFD-E | oL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection |
| Delta C2000 | EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating |
| Delta ASDA-B2 | AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload |
| Hitachi WJ200 | E05 Overload protection · E35 Thermistor |
| Schneider Electric Altivar ATV320 | OLF Motor overload error · OTFL DI6=PTC overheat error |
| INVT Goodrive20 (GD20) | OL1 Motor overload |
| Yaskawa V1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Yaskawa A1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload |
| Yaskawa GA500 | oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Siemens MICROMASTER 420 | F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t |
| Siemens MICROMASTER 430 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Siemens SINAMICS G110 | F0011 Motor over temperature I2t · A0511 Motor over temperature I2t |
| INVT Goodrive200A (GD200A) | OL1 Motor overload |
| Mitsubishi Electric FR-D700 | E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 10 Motor ETR over temperature |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007