MachineryFix

Yaskawa AC drive (VFD) · fault code

GA500 oL1: Motor Overload

oL1 on the Yaskawa GA500 is the “Motor Overload” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.

Code
oL1
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Motor overload or overtemperature

01 / Causes

What causes oL1

  • The load is too large, cycle times are too short, or the motor is overloaded at low speed (a general-purpose motor can overload at low speed even below rated current).
  • L1-01 or E2-01 set wrongly, the V/f pattern or E1-06 (base frequency) wrong, or one drive running several motors.
  • Extra motor loss from overexcitation, wrong speed search settings, input phase loss, or a motor cable that is too long.

02 / Checks

What to check for oL1

In the order Yaskawa gives them.

  1. 01Reduce the load and lengthen C1-01 to C1-08.
  2. 02At low speed, reduce the load or raise the speed; for frequent low-speed running, use a larger or drive-rated motor.
  3. 03Set L1-01 for the motor type, E2-01 to the nameplate current and E1-06 to the rated frequency; adjust the V/f pattern.
  4. 04For several motors on one drive, set L1-01 = 0 and fit a thermal overload relay to each motor.
  5. 05Lower n3-13, set L3-04 to a value other than 4, or set n3-23 = 0.
  6. 06Check all speed search parameters, adjust b3-03 (Speed Search Deceleration Time), and set b3-24 = 1 (Speed Estimation) after Auto-Tuning.
  7. 07Repair any input phase loss; for long motor cables, fit a larger drive or lower C6-02.

Also in the manual

  • oL1 resets only when U4-16 is below 100. L5-07 disables Auto Restart for this fault.

03 / Clearing it

How to clear oL1

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If oL1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor overload or overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare running current with the motor's rating plate current.
  2. 02Check the motor overload settings in the drive against the rating plate.
  3. 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
  4. 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.

05 / Repair

When oL1 means a repair

A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.

If oL1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Motor overload or overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F11 Motor overtemperature · A511 Motor overtemperature I2t
Siemens SINAMICS G120F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature
Siemens SINAMICS V90F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature
Siemens MICROMASTER 440F0011 Motor overtemperature · A0511 Motor overtemperature
Allen-Bradley PowerFlex 525F007 Motor Overload
ABB ACS355F0009 MOT OVERTEMP · A2010 MOTOR TEMP
Delta VFD-EoL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection
Delta C2000EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating
Delta ASDA-B2AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload
Hitachi WJ200E05 Overload protection · E35 Thermistor
Schneider Electric Altivar ATV320OLF Motor overload error · OTFL DI6=PTC overheat error
INVT Goodrive20 (GD20)OL1 Motor overload
Yaskawa V1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Yaskawa A1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload
Siemens MICROMASTER 420F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t
Siemens MICROMASTER 430F0011 Motor overtemperature · A0511 Motor overtemperature
Siemens SINAMICS G110F0011 Motor over temperature I2t · A0511 Motor over temperature I2t
INVT Goodrive200A (GD200A)OL1 Motor overload
Mitsubishi Electric FR-D700E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 10 Motor ETR over temperature

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

oL1 won't clear? Get a technician who knows the GA500.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.