Siemens Servo drive · fault code

SINAMICS V90 F7011: Motor overtemperature

F7011 on the Siemens SINAMICS V90 is the “Motor overtemperature” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.

The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.

Code
F7011
Type
Fault (stops the drive)
Drive
Siemens SINAMICS V90, SIMOTICS S-1FL6
Kind of fault
Motor overload or overtemperature

01 / Causes

What causes F7011

  • The motor is overloaded.
  • The motor's surrounding temperature is too high.
  • A broken wire, or the sensor is not connected.
  • The motor temperature model is set up wrongly.

02 / Checks

What to check for F7011

In the order Siemens gives them.

  1. 01Reduce the motor load.
  2. 02Check the surrounding temperature and the motor's ventilation.
  3. 03Check the wiring and the connection.
  4. 04Check the motor temperature model parameters.

Also in the manual

  • Reaction OFF2: the motor coasts down. Acknowledgement IMMEDIATELY: it clears as soon as the cause is removed.

03 / Clearing it

How to clear F7011

  • Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
  • Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
  • If the cause is not removed, the fault can come back after five seconds with no button pressed.
  • Alarms acknowledge themselves.

Clear it once. If F7011 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor overload or overtemperature faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Compare running current with the motor's rating plate current.
  2. 02Check the motor overload settings in the drive against the rating plate.
  3. 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
  4. 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.

05 / Repair

When F7011 means a repair

A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.

If F7011 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Motor overload or overtemperature: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F11 Motor overtemperature · A511 Motor overtemperature I2t
Siemens SINAMICS G120F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature
Siemens MICROMASTER 440F0011 Motor overtemperature · A0511 Motor overtemperature
Allen-Bradley PowerFlex 525F007 Motor Overload
ABB ACS355F0009 MOT OVERTEMP · A2010 MOTOR TEMP
Delta VFD-EoL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection
Delta C2000EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating
Delta ASDA-B2AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload
Hitachi WJ200E05 Overload protection · E35 Thermistor
Schneider Electric Altivar ATV320OLF Motor overload error · OTFL DI6=PTC overheat error
INVT Goodrive20 (GD20)OL1 Motor overload
Yaskawa V1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Yaskawa A1000oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload
Yaskawa GA500oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload
Siemens MICROMASTER 420F0011 Motor overtemperature I2t · A0511 Motor overtemperature I2t
Siemens MICROMASTER 430F0011 Motor overtemperature · A0511 Motor overtemperature
Siemens SINAMICS G110F0011 Motor over temperature I2t · A0511 Motor over temperature I2t
INVT Goodrive200A (GD200A)OL1 Motor overload
Mitsubishi Electric FR-D700E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm
Danfoss VLT Micro Drive FC 51Alarm 10 Motor ETR over temperature

07 / More codes

Other SINAMICS V90 codes

Source

Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.