F30021 on the Siemens SINAMICS V90 is the “Ground fault” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.
The drive found current leaving the motor circuit through earth: the three output currents no longer add up to zero. The usual cause is damaged insulation in the motor cable, the motor terminal box or the winding, often where water, oil or vibration has reached it.
- Code
- F30021
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V90, SIMOTICS S-1FL6
- Kind of fault
- Earth fault
01 / Causes
What causes F30021
- A ground fault in the power cables.
- A winding fault or ground fault in the motor.
02 / Checks
What to check for F30021
In the order Siemens gives them.
- 01Check the power cable connections.
- 02Check the motor.
Also in the manual
- Reaction OFF2: the motor coasts down. Acknowledgement IMMEDIATELY: it clears as soon as the cause is removed.
03 / Clearing it
How to clear F30021
- Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
- Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
- If the cause is not removed, the fault can come back after five seconds with no button pressed.
- Alarms acknowledge themselves.
Clear it once. If F30021 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How earth fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate the supply, wait for the DC bus to discharge, and disconnect the motor cable at the drive.
- 02Insulation-test each phase of the cable and motor to earth with the drive disconnected (never megger through the drive).
- 03Split the circuit: test the cable alone, then the motor alone, to find which side is low.
- 04Open the motor terminal box and look for moisture, carbon tracking or a chafed lead.
- 05If cable and motor test healthy, check for long or unscreened motor cable and drive filter settings before suspecting the drive.
05 / Repair
When F30021 means a repair
When the cable and motor test healthy and the fault returns with the motor disconnected, the drive's current sensing or output stage is suspect and the unit needs bench testing.
If F30021 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Earth fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F30021 Ground fault |
| Siemens MICROMASTER 440 | F0021 Ground fault |
| Allen-Bradley PowerFlex 525 | F013 Ground Fault · F038 Phase U to Gnd · F039 Phase V to Gnd · F040 Phase W to Gnd |
| ABB ACS355 | F0016 EARTH FAULT |
| Delta VFD-E | GFF Ground fault |
| Delta C2000 | GFF Ground fault |
| Hitachi WJ200 | E14 Ground fault |
| Schneider Electric Altivar ATV320 | SCF3 Ground short circuit error |
| INVT Goodrive20 (GD20) | ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2 |
| Yaskawa V1000 | GF Ground Fault |
| Yaskawa A1000 | GF Ground Fault |
| Yaskawa GA500 | GF Ground Fault |
| Siemens MICROMASTER 430 | F0021 Ground fault |
| INVT Goodrive200A (GD200A) | ETH1 To-ground short-circuit fault 1 · ETH2 To-ground short-circuit fault 2 |
| Mitsubishi Electric FR-D700 | E.GF Output side earth (ground) fault overcurrent at start |
| Danfoss VLT Micro Drive FC 51 | Alarm 14 Earth (ground) fault · Alarm 44 Earth fault 2 |
07 / More codes
Other SINAMICS V90 codes
Source
Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007