Uv1 on the Yaskawa V1000 is the “DC Bus Undervoltage” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.
- Code
- Uv1
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- DC bus undervoltage
01 / Causes
What causes Uv1
- While running, the DC bus voltage fell below the undervoltage level (L2-05): about 190 V on 200 V class (160 V single-phase), about 380 V on 400 V class (350 V when E1-01 is below 400).
- A missing input phase, a loose input terminal, a supply voltage problem or interruption, worn internal circuitry, a supply transformer too small, air inside the drive too hot, or a CHARGE indicator problem.
02 / Checks
What to check for Uv1
In the order Yaskawa gives them.
- 01Check and correct the main circuit input wiring, and tighten the terminals to the torque in the manual.
- 02Check the supply voltage is within the drive's specification and correct any interruption.
- 03Check the capacitor maintenance time (U4-05) and replace the drive if it is above 90%.
- 04Check the supply transformer's capacity.
- 05Check the drive's internal temperature.
- 06If the CHARGE indicator is faulty, replace the drive.
Also in the manual
- The fault is output only when L2-01 = 0, or when L2-01 = 1 and the voltage stays below L2-05 for longer than L2-02.
03 / Clearing it
How to clear Uv1
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If Uv1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus undervoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
- 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
- 03Look for loose or heat-discoloured supply terminals.
- 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.
05 / Repair
When Uv1 means a repair
A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.
If Uv1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
DC bus undervoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active |
| Siemens SINAMICS G120 | F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging |
| Siemens SINAMICS V90 | F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off |
| Siemens MICROMASTER 440 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Allen-Bradley PowerFlex 525 | F003 Power Loss · F004 UnderVoltage |
| ABB ACS355 | F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage |
| Delta VFD-E | Lv Low voltage · dEb Deceleration energy backup error |
| Delta C2000 | LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error |
| Delta ASDA-B2 | AL003 Under voltage |
| Hitachi WJ200 | E09 Under-voltage error |
| Schneider Electric Altivar ATV320 | USF Supply mains undervoltage error |
| INVT Goodrive20 (GD20) | UV Bus undervoltage · PoFF System power off |
| Yaskawa A1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa GA500 | Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage |
| Siemens MICROMASTER 420 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Siemens MICROMASTER 430 | F0003 Undervoltage · A0503 Undervoltage limit value |
| Siemens SINAMICS G110 | F0003 Undervoltage · A0503 Undervoltage limit |
| INVT Goodrive200A (GD200A) | UV Bus undervoltage · PoFF System power failure |
| Mitsubishi Electric FR-D700 | UV Undervoltage |
| Danfoss VLT Micro Drive FC 51 | Alarm 8 DC under voltage |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007