Delta AC drive (VFD) · fault code

C2000 LvS: Low-voltage at stop

LvS on the Delta C2000 is the “Low-voltage at stop” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.

Code
LvS
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
DC bus undervoltage

01 / Causes

What causes LvS

  • A power cut.
  • The drive model does not match the supply.
  • The supply voltage varies.
  • Starting a large motor on the same supply.
  • The DC bus needs a DC reactor.
  • A hardware failure in voltage detection.

02 / Checks

What to check for LvS

In the order Delta Electronics gives them.

  1. 01Improve the power supply.
  2. 02Check the supply specification matches the drive.
  3. 03Bring the supply voltage within the drive's range, then switch the power off and on. If it is still there, Delta's instruction is to return the drive to the factory for repair.
  4. 04Check the power system, or increase the capacity of the power equipment.
  5. 05Install a DC reactor.

Also in the manual

  • Fault ID 14. The DC bus is below Pr. 06-00 while stopped. It resets manually or by itself once the DC bus recovers above the low-voltage level by the margin the manual gives for each voltage series and frame.

03 / Clearing it

How to clear LvS

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If LvS comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How dc bus undervoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
  2. 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
  3. 03Look for loose or heat-discoloured supply terminals.
  4. 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.

05 / Repair

When LvS means a repair

A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.

If LvS keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

DC bus undervoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active
Siemens SINAMICS G120F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging
Siemens SINAMICS V90F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off
Siemens MICROMASTER 440F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Allen-Bradley PowerFlex 525F003 Power Loss · F004 UnderVoltage
ABB ACS355F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage
Delta VFD-ELv Low voltage · dEb Deceleration energy backup error
Delta ASDA-B2AL003 Under voltage
Hitachi WJ200E09 Under-voltage error
Schneider Electric Altivar ATV320USF Supply mains undervoltage error
INVT Goodrive20 (GD20)UV Bus undervoltage · PoFF System power off
Yaskawa V1000Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage
Yaskawa A1000Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage
Yaskawa GA500Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage
Siemens MICROMASTER 420F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active
Siemens MICROMASTER 430F0003 Undervoltage · A0503 Undervoltage limit value
Siemens SINAMICS G110F0003 Undervoltage · A0503 Undervoltage limit
INVT Goodrive200A (GD200A)UV Bus undervoltage · PoFF System power failure
Mitsubishi Electric FR-D700UV Undervoltage
Danfoss VLT Micro Drive FC 51Alarm 8 DC under voltage

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007