LvA on the Delta C2000 is the “Low-voltage during acceleration” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.
- Code
- LvA
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- DC bus undervoltage
01 / Causes
What causes LvA
- A power cut.
- The supply voltage varies.
- Starting a large motor on the same supply.
- The load is too large.
- The DC bus needs a DC reactor.
- No short-circuit plate or DC reactor between terminals +1 and +2.
02 / Checks
What to check for LvA
In the order Delta Electronics gives them.
- 01Improve the power supply.
- 02Bring the supply voltage within the drive's range.
- 03Check the power system, or increase the capacity of the power equipment.
- 04Reduce the load, fit a larger drive, or lengthen the acceleration time.
- 05Install a DC reactor.
- 06Fit the short-circuit plate or a DC reactor between terminals +1 and +2. If it is still there, Delta's instruction is to return the drive to the factory for repair.
Also in the manual
- Fault ID 11. The DC bus fell below Pr. 06-00 while accelerating. Resets once the DC bus is back above Pr. 06-00 plus 30 V (frames A to D) or 40 V (frame E and above).
03 / Clearing it
How to clear LvA
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If LvA comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus undervoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
- 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
- 03Look for loose or heat-discoloured supply terminals.
- 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.
05 / Repair
When LvA means a repair
A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.
If LvA keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
DC bus undervoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active |
| Siemens SINAMICS G120 | F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging |
| Siemens SINAMICS V90 | F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off |
| Siemens MICROMASTER 440 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Allen-Bradley PowerFlex 525 | F003 Power Loss · F004 UnderVoltage |
| ABB ACS355 | F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage |
| Delta VFD-E | Lv Low voltage · dEb Deceleration energy backup error |
| Delta ASDA-B2 | AL003 Under voltage |
| Hitachi WJ200 | E09 Under-voltage error |
| Schneider Electric Altivar ATV320 | USF Supply mains undervoltage error |
| INVT Goodrive20 (GD20) | UV Bus undervoltage · PoFF System power off |
| Yaskawa V1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa A1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa GA500 | Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage |
| Siemens MICROMASTER 420 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Siemens MICROMASTER 430 | F0003 Undervoltage · A0503 Undervoltage limit value |
| Siemens SINAMICS G110 | F0003 Undervoltage · A0503 Undervoltage limit |
| INVT Goodrive200A (GD200A) | UV Bus undervoltage · PoFF System power failure |
| Mitsubishi Electric FR-D700 | UV Undervoltage |
| Danfoss VLT Micro Drive FC 51 | Alarm 8 DC under voltage |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007