MachineryFix

Delta Servo drive · alarm code

ASDA-B2 AL002: Over voltage

AL002 on the Delta ASDA-B2 is the “Over voltage” alarm. This alarm switches the servo off, so the motor is no longer driven until the alarm is cleared.

The voltage on the drive's internal DC bus rose above its limit. Either the incoming supply is too high, or the motor is feeding energy back into the drive because the load is being slowed faster than friction alone would slow it, or an overhauling load is driving the motor.

Code
AL002
Type
Alarm (stops the drive)
Drive
Delta ASDA-B2
Kind of fault
DC bus overvoltage

01 / Causes

What causes AL002

  • The main circuit input voltage is above the rated allowable voltage.
  • The wrong power supply for the drive.
  • The servo drive's hardware is damaged.

02 / Checks

What to check for AL002

In the order Delta Electronics gives them.

  1. 01Measure the main circuit input voltage with a voltmeter and check it is within the rated range (chapter 10.1). Use the correct supply, or a voltage regulator in series.
  2. 02Check with a voltmeter that the power system matches the drive's specification, and use the correct supply.
  3. 03If the input voltage is within range and the alarm still shows, Delta's instruction is to send the drive back to the distributor or contact Delta.

Also in the manual

  • The main circuit voltage is higher than the standard voltage. ALM output; servo off. Clears by turning on the alarm reset input (DI.ARST).

03 / Clearing it

How to clear AL002

  • Remove the cause first. Most alarms clear by turning on the alarm reset input, DI.ARST (assigned to DI5 by default).
  • Some alarms clear only after the drive is powered off and on: AL004, AL011, AL024 to AL029, AL031 and AL035. AL003 also needs a power cycle, unless P2-66 bit 2 is set so it clears once the voltage is back to normal.
  • AL013 clears by itself once the emergency stop input (DI.EMGS) is off. AL014 and AL015 clear with DI.ARST, by switching the servo off, or by moving the motor back off the limit.
  • AL099 clears by setting P2-08 to 30, then to 28, and powering the drive off and on. For AL555 and AL880, do nothing to the drive: Delta's instruction is to send it back to the distributor or contact Delta.

Clear it once. If AL002 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How dc bus overvoltage faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Note when it trips. Overvoltage while stopping almost always means regenerated energy; overvoltage at standstill points at the supply.
  2. 02Measure the incoming supply between phases, at the drive terminals, during the time the trip happens.
  3. 03Compare the deceleration time with the inertia of the load: fans, flywheels and loaded conveyors need long ramps or a braking resistor.
  4. 04If a braking resistor is fitted, check its resistance and wiring and that the braking function is enabled in the drive.

05 / Repair

When AL002 means a repair

If the supply is normal, the ramp is long and the fault still appears, the braking chopper, the resistor or the drive's voltage measurement may have failed.

If AL002 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

DC bus overvoltage: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F2 Overvoltage · A502 Overvoltage limit · A910 Vdc_max controller deactivated · A911 Vdc_max controller active
Siemens SINAMICS G120F30002 DC-link voltage overvoltage · A07400 DC-link voltage maximum controller active · A30502 DC-link overvoltage
Siemens SINAMICS V90F7404 Upper DC link voltage threshold reached · F30002 DC link voltage, overvoltage
Siemens MICROMASTER 440F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Allen-Bradley PowerFlex 525F005 OverVoltage
ABB ACS355F0002 DC OVERVOLT · A2002 OVERVOLTAGE
Delta VFD-Eov Over-voltage
Delta C2000ovA Over-voltage during acceleration · ovd Over-voltage during deceleration · ovn Over-voltage at constant speed · ovS Over-voltage at stop
Hitachi WJ200E07 Over-voltage protection · E15 Input over-voltage
Schneider Electric Altivar ATV320OBF DC bus overvoltage error · OSF Supply mains overvoltage error
INVT Goodrive20 (GD20)OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running
Yaskawa V1000ov Overvoltage
Yaskawa A1000ov Overvoltage
Yaskawa GA500ov Overvoltage
Siemens MICROMASTER 420F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens MICROMASTER 430F0002 Overvoltage · A0502 Overvoltage limit value · A0910 Vdc-max controller disabled/switched-out · A0911 Vdc-max controller active
Siemens SINAMICS G110F0002 Overvoltage · A0502 Overvoltage limit · A0910 Vdc-max controller de-activated · A0911 Vdc-max controller active
INVT Goodrive200A (GD200A)OV1 Overvoltage during acceleration · OV2 Overvoltage during deceleration · OV3 Overvoltage during constant speed running
Mitsubishi Electric FR-D700E.OV1 Regenerative overvoltage trip during acceleration · E.OV2 Regenerative overvoltage trip during constant speed · E.OV3 Regenerative overvoltage trip during deceleration or stop · oL Stall prevention (overvoltage)
Danfoss VLT Micro Drive FC 51Alarm 7 DC overvoltage

07 / More codes

Other ASDA-B2 codes

Source

Delta Electronics, ASDA-B2 Standard AC Servo Drive User Manual, Revision May 2018, DELTA_IA-ASDA_B2_UM_EN_20180509, Chapter 9, Troubleshooting (9.1 to 9.3).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

AL002 won't clear? Get a technician who knows the ASDA-B2.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.