oL on the Delta C2000 is the “Over load” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.
- Code
- oL
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- Drive overload
01 / Causes
What causes oL
- The load is too large.
- The acceleration or deceleration time, or the working cycle, is too short.
- The V/F voltage is too high.
- The drive is too small.
- Overload during low-speed running.
- Torque compensation too large, or stall prevention set wrongly.
- An output phase is lost.
- Speed tracking set wrongly (including restart after a momentary power loss or after a fault).
02 / Checks
What to check for oL
In the order Delta Electronics gives them.
- 01Reduce the load.
- 02Lengthen the acceleration and deceleration times (Pr. 01-12 to 01-19).
- 03Adjust the V/F curve (Pr. 01-01 to 01-08), especially the mid-point voltage, and see the V/F curve selection in Pr. 01-43. A mid-point voltage set too low reduces the load capacity at low speed.
- 04Fit a larger drive.
- 05Reduce the load at low speed, fit a larger drive, or lower the carrier frequency (Pr. 00-17).
- 06Lower the torque compensation gain (Pr. 07-26) until the output current drops and the motor does not stall. Set stall prevention to a suitable value.
- 07Check the three-phase motor, and the cable for breaks or loose screws.
- 08Correct the speed tracking settings: turn on speed tracking, and adjust its maximum current (Pr. 07-09).
Also in the manual
- Fault ID 21. The drive can deliver 120% of its rated output current for 1 minute; beyond its overload and derating curves it trips. Reset manually, 5 seconds after the fault has cleared.
03 / Clearing it
How to clear oL
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If oL comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overload faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Record the running current and compare it with the drive's rated current.
- 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
- 03Check acceleration time and boost settings; long periods at high torque add up quickly.
05 / Repair
When oL means a repair
If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.
If oL keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Drive overload: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F5 Inverter I2t · A505 Inverter I2t |
| Siemens SINAMICS G120 | F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t |
| Siemens SINAMICS V90 | F30005 Power unit: Overload I2t |
| Siemens MICROMASTER 440 | F0005 Inverter I2T · A0505 Inverter I2T |
| Allen-Bradley PowerFlex 525 | F064 Drive Overload |
| Delta VFD-E | oL Overload |
| Hitachi WJ200 | E38 Low-speed overload protection |
| INVT Goodrive20 (GD20) | OL2 VFD overload |
| Yaskawa V1000 | oL2 Drive Overload |
| Yaskawa A1000 | oL2 Drive Overload |
| Yaskawa GA500 | oL2 Drive Overload |
| Siemens MICROMASTER 420 | F0005 Inverter I2t · A0505 Inverter I2t |
| Siemens MICROMASTER 430 | F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle |
| Siemens SINAMICS G110 | F0005 Inverter I2t · A0505 Inverter I2t |
| INVT Goodrive200A (GD200A) | OL2 VFD overload |
| Mitsubishi Electric FR-D700 | E.THT Inverter overload trip (electronic thermal O/L relay function) |
| Danfoss VLT Micro Drive FC 51 | Alarm 9 Inverter overloaded |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007